Indoor VCB
Product Description
ItemDescriptionUnitData
1Rated voltageKV12
2Max. voltageKV12
3Rated currentA1250/1600/2000/2500/3150
4Rated break current on shortingKA31.5/40/50
5Rated short circuit making currentKA80/100/125
6Rated peak withstand currentKA80/100/125
74S Rated withstand currentKA31.5/40/50
8Rated insulation levelPower frequency voltage(when losing a circuit)KVDreaker 48
Impulse withstand voltage(when losing a circuit)Dreaker 84
9Rated operating sequence
OC-0.3s-CO-180S-CO
10Mechanical lifeTimes10000
11Open circuit times of rated short dropout currentTimes50
12Rated close brake voltage of operating machnieV110,220
13Rated break brake voltage of operating machnieV110,220
14Clearance between open contactsmm11±1
15Exceed range(the compress length of contact sping)mm4±0.5
16Different period of three-phase break and close breakms≤2
17The jump time of contact close breakms≤2
18Average break speedm/s0.9~1.2
19Average closing speedm/s0.6~1.2
20Opening timeUbder max.operating voltageS≤0.05
Under min.operating voltage≤0.08
21Closing times≤0.1
22Resistance of each phase main loopμΩ≤40
23Contacts limit ersionmm3